Description
PN: 800-DCSS-SS
DC Surge Suppressor. Outdoor DC Powerline surge suppressor – protector. Protects input and output separately.
Lumped inductance
Lumped inductance between input and output chokes surges coming from flowing through. Gas discharge tubes then shunt the surge to ground while impeding their flow to the other side of the device. Both semiconductor surge suppression and Gas Discharge Tube for fast and large surge protection. Double Multi-Stage protection devices provide 4 X the protection of conventional protection devices.
Center ground post is to be connected to earth ground
See all of our innovative surge suppression products
Specifications (per port, double these specs for total protection)
Center ground post is to be connected to earth ground
Electrical Specifications
- Operating Voltage
- 0-55 VDC
- DC Spark-over Voltage: 90+/-20%
- Max. Impulse Breakdown Voltage:
- 100V/S (v) 500, 1KV/us(v) 600
- Max. Impulse Discharge Current (8/20us)
- 1 Time 10 KA
- 10 Times 5 KA
- Impulse Life (10/1000us)
- 300 Times 100A
- Normal Alternating Discharge Current
- 60Hz 1 Sec 5 amps
- Single 9 Cycles 30 amps
- DC Holdover Voltage
- 52 Volts
- Minimum Insulation Resistance
- 1 G Ohm
- Maximum Capacitance (1 MHz)
- 2pf
Applications
Any DC powered equipment up to 55 VDC.
Center ground post is to be connected to earth ground